How Fire Alarm Systems Connect to Elevator Recall Systems


A fire alarm system can initiate elevator recall by sending a signal to the elevator controls when a designated fire alarm device activates. The elevator controller then performs its programmed emergency operation, typically recalling cars to a designated landing and taking them out of normal service. The exact sequence depends on the building’s approved design, elevator equipment, and local requirements.
In California, this emergency operation is known as Phase I Emergency Recall Operation. The state defines it as an automatic or manual recall of an elevator to a specific landing, removing it from normal service because firefighters’ service has been activated. California Code of Regulations, Title 8, Section 3009
How the Fire Alarm and Elevator Systems Work Together
The fire alarm system and elevator controller are separate systems that communicate through an approved interface. When a designated initiating device detects a condition, the fire alarm system sends a signal to the elevator controls. The elevator controller carries out the recall sequence.
The fire alarm design identifies which devices initiate recall and what signals the elevator controls should receive. Not every alarm device in a building necessarily triggers elevator recall. The approved plans and sequence of operations define the response.
Common devices that may initiate recall
Depending on the building design and applicable code, recall may be initiated by devices associated with elevator lobbies, machine rooms, control spaces, or hoistways. California’s building and fire codes govern where detection is required, and the AHJ reviews the design. The California State Architect’s guidance for its projects describes smoke detectors serving Phase I recall as being installed in designated elevator areas. DSA Interpretation of Regulations 30-1
What Happens During Elevator Recall?
Phase I: Emergency recall
When a designated recall device activates—or a manual recall control is used—the system sends the programmed signal to the elevator controller. Cars are directed to the designated recall landing and removed from normal passenger service. If the designated landing is affected by the initiating condition, the approved sequence may send cars to an alternate landing.
The California State Fire Marshal’s code interpretation defines Phase I as automatic or manual recall to a specified landing. The building’s approved design determines the exact recall destinations and signals. California Code of Regulations, Title 8, Section 3009
Phase II: Firefighter in-car operation
Phase II is a separate mode that allows firefighters to operate an elevator from inside the car using designated controls. It follows Phase I recall and is governed by elevator safety requirements. California distinguishes Phase II emergency in-car operation from the initial recall phase. California Code of Regulations, Title 8, Section 3009
Why Coordination Between Contractors Matters
Fire alarm and elevator contractors work on different equipment, but their work must produce one coordinated, tested sequence. The fire alarm contractor handles the detection devices, programming, and interface signals within its scope. The elevator contractor handles elevator controls and operation. The design team and AHJ establish and review project requirements.
Before installation or modification, confirm:
Which devices initiate elevator recall
The designated and alternate recall landings
How the interface signal reaches the elevator controller
Which status signals or supervisory conditions are monitored
Whether sprinklers, heat detectors, or power-disconnect functions affect the sequence
Who supplies and installs each interface component
Who coordinates acceptance testing and closeout records
The California Division of Occupational Safety and Health advises elevator owners that certain elevator safety tests involving fire alarm sensors require coordination between the alarm testing company and elevator service company so both can be present. Cal/OSHA elevator owner guidance
Testing the Elevator Recall Sequence
Testing should confirm that the initiating devices, fire alarm programming, interface, elevator controller, and recall destinations operate as designed. The test team should compare actual operation with the approved sequence and document results and any corrections.
In the City of Los Angeles, published testing guidance assigns roles to LADBS and LAFD for life-safety system inspection and testing. Procedures vary by jurisdiction, building, and project, so confirm the applicable process with the AHJ. LADBS fire alarm systems testing guidance
When to Review or Update an Existing System
Consider a fire alarm and elevator recall review when:
The fire alarm panel, elevator controller, or interface is replaced
Elevator equipment or recall landings change
Building renovations affect elevator lobbies or detection devices
A fire alarm or elevator test identifies a failure
A deficiency notice or plan review requests changes
The existing sequence or drawings are missing or unclear
Do not assume an older system’s operation matches current project requirements. Have qualified contractors review the equipment, available records, and applicable AHJ requirements before making changes.
Why Choose Cyber Shield Security?
Fire alarm and elevator recall projects require careful coordination between property teams, fire alarm contractors, elevator contractors, and local officials. Cyber Shield Security works with property owners, managers, apartment building owners, general contractors, developers, and businesses on fire alarm service and installation projects.
A project review can help clarify the existing fire alarm equipment, interface needs, scope of work, and coordination steps for your building.
Frequently Asked Questions
Does every fire alarm activation recall the elevators?
No. The approved system design specifies which initiating devices activate the elevator recall sequence. A general building alarm and an elevator recall signal are not automatically the same event.
Which fire alarm devices can trigger elevator recall?
Depending on the building and approved design, designated devices may be located in elevator lobbies, machine rooms, control spaces, or hoistways. The AHJ-approved plans and sequence determine which devices initiate recall.
What is the difference between Phase I and Phase II elevator operation?
Phase I recalls elevators to a designated landing and removes them from normal passenger service. Phase II is firefighter in-car operation using designated controls.
Who installs the connection between the fire alarm and elevator controls?
Responsibility depends on the project documents and the contractors’ scopes. Confirm who provides, installs, programs, and tests each component of the interface before work begins.
Do both the fire alarm and elevator contractors need to attend testing?
Coordination is often needed because both systems must operate together. Cal/OSHA specifically notes that certain elevator safety tests involving fire alarm sensors require coordination between the alarm testing company and elevator service company.
Can an elevator recall system be tested during normal building operations?
Testing must be scheduled and coordinated with building management, the fire alarm contractor, elevator contractor, occupants, and AHJ as required. Confirm the test plan and any operational impacts before the test.
Do elevator recall requirements differ between Los Angeles-area cities?
The applicable AHJ, adopted code provisions, and project requirements can vary. Confirm requirements for the property address in Los Angeles, North Hollywood, Studio City, Burbank, Sierra Madre, Arcadia, Pasadena, Woodland Hills, Sherman Oaks, Santa Monica, Beverly Hills, or West Hollywood.